Simply, fix the control panel to the wall, connect the
field wiring and everything else is configured in the
software. Even programming the control panel is
simple. No computer is required and it only takes a
few key presses to have a working fire alarm system.
First, set the panel to “AUTOLEARN” Second “RESET”
the panel. The Control Panel is now protecting the
building.
The Dimension series provides additional features
allowing:- programmable text messages to identify
the exact location of each field device, a class change
input for schools, coincidence and verification
detection (false alarm management), sensitivity
adjustment (between day and night), programmable
function buttons, input/output logic and extensive
event logging. A feature rich fire alarm control panel
constructed from high specification components to
help both the installer and the end user.
The Dimension series is especially suited to offices,
retail units, health centres, leisure facilities, cinemas
and hotels to name but a few applications. A compact,
high performance, economical fire alarm control
panel for the protection of medium sized buildings.
• Complies with EN54 part 2 and part 4
• 40 fire zone LED indicators
• 2 independent sounder circuits
• 500mA Loop Drivers
• 7 day timers
• Day/Night mode switching
• Onboard monitored inputs
• Programmable user function keys
• Event logging
• Onboard diagnostics
• User access restriction
• All metal enclosure
• Plug-in connectors
• Optional internal printer
• PC configuration software (optional)
mechanical
Dimension (H x W x D) :
DX4e-40L 620 x 380 x 130 mm
DX4e-40LP 620 x 380 x 130 mm
Weight (Excluding batteries):
DX4e-40L(F) 9 Kg
DX4e-40LP(F) 9.2 Kg
Material : 1.2mm Zintec powder epoxy coated
Colour : RAL 9001 - Cool Grey
Knockouts :
Top: 19 x M20
Bottom: 3 x M20
Temperature
Operating : 0°C to +45°C
Storage : -10°C to +55°C
Relative humidity : 5% to 95% non-condensing
electrical
Operating Voltage : 230Vac (+10%, -15%) 50-60 Hz
PSU Rating :
DX4e-40L(F) 24 Vdc 4A
DX4e-40LP(F) 24 Vdc 4A
Stand-by Batteries :
DX4e-40L(F) 2 x 12AHr or 2 x 17AHr
DX4e-40LP(F) 2 x 12AHr or 2 x 17AHr
Auxiliary output *: +24 Vdc 250mA fused
Loop Capacity*: 4 Loops, 500mA per loop
198 devices per loop, Morley-IAS Protocol
Output Relays:
Fire relay : Single pole changeover 30Vdc 1A
Fault relay : Single pole changeover 30Vdc 1A
Aux relay : Programmable single pole
changeover 30Vdc 1A
Onboard Inputs:
Keyswitch : programmable for select functions
Input #1 : programmable (monitored) for select functions
Input #2 : programmable (monitored) for select functions
Data Ports : 1 x RS 485 (Repeater connections)
1 x RS232 (PC Programming)
Sounder Circuits : 2 output circuits, 1A available across
both sounder circuits.*