Home --> FireLite
CP 355 A
  • General
  • Feature
  • Specification
The CP355(A) addressable, low-profile, plug-in ionization detector uses a state-of-the-art ionization sensing chamber to provide open-area protection and is used exclusively with Fire•Lite’s addressable Fire Alarm Control Panels (FACPs). The ionization detector is used to sense products-of-combustion and report the measured level of such products to the fire alarm control panel. Since this detector is addressable, it will help emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (P/N RA400Z).

SLC loop:

• Two-wire loop connection.

• Unit uses base for wiring.

Addressing:

• Addressable by device.

• Direct Decade entry of address: 01 – 99 with MS-9200, MS-

9200UD and MS-9200UDLS and 01 – 159 with MS-9600

and MS-9600UDLS.

Architecture:

• Unique single-source, dual-chamber design to respond

quickly and dependably to a broad range of fires.

• Sleek, low-profile design.

• Integral communications and built-in type identification.

• Built-in tamper-resistant feature.

• Removable cover and insect-resistant screen for simple

field cleaning.

Operation:

• Withstands air velocities up to 1,200 feet-per-minute (6.1 m/

sec.) without triggering a false alarm.

• Factory preset at 1.5% nominal sensitivity for panel alarm

threshold level.

• Visible LED “blinks” when the unit is addressed (communicating

with the fire panel) and latches on in alarm.

Mechanicals:

• Sealed against back pressure.

• Direct surface mounting or electrical box mounting.

• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16

cm) octagonal box, or 4.0" (10.16 cm) square electrical box

(using a plaster ring).

Voltage range: 15 – 32 VDC (peak).

Standby current: 300 μA @ 24 VDC.

LED current: 6.5 mA @ 24 VDC (latched “ON”).

Air velocity: 1,200 ft./min. (6.1 m/sec.) maximum.

Diameter: 6.1 inches (15.5 cm) installed in B350LP(A) base

//