System Sensor 200 Series intelligent plug-in smoke detectors with integral communication
provide features that surpass conventional detectors. Detector sensitivity can be programmed
in the control panel software. Sensitivity is continuously monitored and reported to the panel.
Point ID capability allows each detector’s address to be set with decade address switches,
providing exact detector locations for selective maintenance when chamber contamination
reaches an unacceptable level.
-
Height
2.0 inches (51 mm)
Diameter
6.1 inches (155 mm)
installed in B210LP base
4.1 inches (104 mm)
installed in B501 base
Shipping Weight
Heat: 4.8 oz. (136 g)
Photo/Photo with Heat: 5.2oz. (147 g)
Ion: 5.4 oz. (153 g)
Operating Temperature Range
Ion/Photo: 32° to 120°F (0° to 49°C)
Photo with Thermal: 32° to 100°F
(0° to 38°C)
Thermal: –4° to 100°F (–20° to 38°C)
High Temperature: –4 to 150ºF
(–20 to 66ºC)
UL Listed Velocity Range
Ion: 0 – 1200 fpm (0 – 6.1 m/sec)
Photo/Photo with Thermal:
0 – 4000 fpm (0 – 20 m/sec)
(suitable for installation in ducts)
Insect Screen Hole Size
Photo – 0.016 inch (0.41mm) nominal
Ion – 0.035 inch (0.89mm) nominal
Relative Humidity
10% – 93% noncondensing
Thermal Ratings
Fixed Temperature Setpoint:
135°F (57°C)
Rate of Rise Detection: 15°F/min.
(8.3°C/min.)
High Temperature Heat: 190ºF (88ºC)
Voltage Range
15 – 32 volts DC peak
Standby Current (max. avg.)
Ion/Thermal: 150 μA @ 24 VDC
(without communication, LED off)
200 μA @ 24 VDC (one communication
ever y 5 sec. with LED enabled)
Photo/Photo with Thermal: 250 μA @
24 VDC (without communication, LED
off)
300 μA @ 24 VDC (one communication
ever y 5 sec. with LED enabled)
LED Current (max.)
6.5 mA @ 24 VDC (on)