The ECO1002 multi-criteria detector is
state of the art optical chamber and a class
A1R thermal element combined with a
microprocessor, running sophisticated algorithms
to provide quick and accurate detection of fires.
The combination of photoelectric and thermal
characteristics provides a faster response to 'real
fire' situations, while at the same time reducing
the risk of unwanted environmentally generated
alarms.
A laser-based hand held Remote Test Unit can be
used in conjunction with the range of ECO1000
detectors for alarm test purposes. The unit
transmits a coded message, preventing spurious
alarms being generated by other laser based
devices. With a range of several metres, the hand
held test unit provides an effortless way of
remotely testing the range of ECO1000 detectors
and removes the need for any direct physical
access to the detector by the user
• Low profile design
• Low current draw
• Operates on12 and 24VDC Systems
• Remote alarm test feature
• Easy Maintenance
• Range of detector bases available
• Remote LED Option
• LPCB & VDS Approved to EN54 Pt.7& Pt.5. Also approved to CEA 4021
• Extended warranty
electrical
Operating Voltage Range
8 to 30 VDC (Nominal 12/24VDC)
Typical Standby Current
240µA @ 24VDC
Maximum Permissible Alarm Current
50mA (current limited by control panel)
environmental
Operating Temperature Range
(see note 1)
-30°C to +70°C
Storage Temperature Range
-40°C to +85°C
Humidity
5 to 95% Relative Humidity (non-condensing)
mechanical
Height (without Base)
40.5mm
Diameter
102mm
Weight
75g
Max Wire Gauge for Terminals
2.0mm
Colour
Approximates to RAL9016
Material
ABS