Duct smoke detector accessories add functionality to the duct
smoke detection system by allowing quick, convenient inspections
at eye level and effective audible and visible notification options. All
System Sensor duct smoke detectors and accessories are UL listed.
The APA151 piezo annunciator, which replaces the APA451 with
a new, improved look, provides an audible alarm signal, a red LED
to indicate alarm status, and a green LED to indicate power status.
It is intended for use with System Sensor 4-wire conventional duct
smoke detector applications without a system control panel, to
comply with NFPA 90A.
The MHR and MHW SpectrAlert® Advance mini-horns feature
temporal or continuous tones at high and low volume settings.
Their small footprint allows mounting to single-gang back boxes for
applications where a small device is desired.
The RA100Z and RA100ZA remote annunciators are designed
for both conventional and intelligent applications. Their red LED
provides visual indication of an alarm condition.
The RTS151 and RTS151KEY remote test stations are automatic
fire detector accessories designed to test duct smoke detectors
from a convenient location. For 4-wire detectors, the RTS151KEY test
station features a multi-colored LED that alternates between steady
green and red. For 2-wire detectors, the LED illuminates red for alarm.
The RTS2 and RTS2-AOS multi-signaling accessories are designed
to work with InnovairFlex 4-wire conventional duct smoke detectors.
These accessories include a key switch that can be used to select
one of two connected sensors to be tested, reset, or both by a push
button switch. They also enable sensitivity measurements using
the SENS-RDR sensitivity reader (sold separately). The AOS (Add-On
Strobe) is an optional accessory included with the RTS2-AOS model.
-
APA151 Piezo Annunciator
Voltage Regulated 24 VDC
Operating Voltage 16 to 33 VDC
Maximum Alarm Current 30 mA
Temperature Range 0°C to 49°C (32°F to 120°F)
Relative Humidity 10 to 93% non-condensing
Wire Gauge 12 to 18 AWG
Dimensions 4.6˝ H × 2.9˝ W × .45˝ D
MHR/MHW SpectrAlert® Advance Mini-Horns
Voltage Regulated 12 DC or FWR (Full Wave Rectified)
or Regulated 24 VDC or FWR
Operating Voltage 8 to 33 VDC
(9 to 33 VDC with Sync•Circuit™ Module)
Sounder Current Draw 22 mA RMS max. at 8 to 17.5 Volts DC
17 mA RMS max. at 8 to 17.5 Volts FWR
29 mA RMS max. at 16 to 33 Volts DC
25 mA RMS max. at 16 to 33 Volts FWR
Temperature Range 0°C to 49°C (32°F to 120°F)
Humidity Range 10 to 93% non-condensing
Nominal Sounder Frequency 3 kHz
Wire Gauge 12 to 18 AWG
Dimensions 4.6˝ H × 2.9˝ W × 0.45˝ D
RA100Z/RA100ZA Remote Annunciator
Voltage Range Conventional System: 3.1 to 32 VDC
Intelligent System: 18 to 32 VDC
Maximum Alarm Current 12 mA
Dimensions 4.6 ˝ H × 2.8˝ W × 1.3˝ D
RTS151 Remote Test Station
Power Requirements Alarm LED: 2.8 to 32 VDC, 12 mA max.
Total Current: 105 mA max.
Test Switch 10 VA @ 32 VDC
Reset Switch 10 VA @ 32 VDC
Alarm Response Time 40 seconds max.
Temperature Range –10°C to 60°C (14°F to 140°F)
Relative Humidity 95% non-condensing
Wire Gauge 14 to 18 AWG
Dimensions 4.8˝ H x 2.90˝ W x 1.4˝ D
RTS151KEY Remote Test Station with Key
Power Requirements Power LED (Green): 14 to 35 VDC, 12 mA max.
Alarm LED (Red): 2.8 to 32 VDC, 12 mA max.
Total Current: 105 mA max.
Alarm Response Time 40 seconds max.
Temperature Range –10°C to 60°C (14°F to 140°F)
Relative Humidity 95% non-condensing
Wire Gauge 14 to 18 AWG
Dimensions 4.6˝ H × 2.75˝ W × 1.8˝ D
RTS2 and RTS2-AOS Multi-signaling Accessory
Voltage 20 to 29 VDC
Power Requirements Standby: 3.0 mA max.
Trouble: 16.0 mA max.
Alarm without strobe: 30 mA max.
Alarm with strobe: 55 mA max.
Sounder 85 dBA at ten feet
Temperature Range –10°C to 60°C (14°F to 140°F)
Relative Humidity 95% non-condensing
Wire Gauge 14 to 22 AWG
Dimensions 4.8˝ W x 5.3˝ H x 1.6˝ D