The SpectrAlert Advance series of notification appliances is
designed to simplify installations, with features such as plug in
designs, instant feedback messages to ensure correct installation of
individual devices, and 11 field-selectable candela settings for wall
and ceiling strobes and horn/strobes.
When installing Advance products, first attach a universal mounting
plate to a four-inch square, four-inch octagon or double-gang
junction box. The two-wire mounting plate attaches to a single-gang
junction box.
Next, connect the notification appliance circuit wiring to the SEMS
terminals on the mounting plate.
• Electrically compatible with existing SpectrAlert products
• Automatic selection of 12- or 24-volt operation at 15 and 15/75
candela
• Plug-in design
• Field selectable candela settings on wall and ceiling units: 15, 15/75,
30, 75, 95, 110, 115, 135, 150, 177, 185
• Same mounting plate for wall- and ceiling-mount units
• Shorting spring on mounting plate for continuity check before
installation
• Tamper resistant construction
• Outdoor wall and ceiling products rated from –40°F to 151°F
• Design allows minimal intrusion into the back box
• Horn rated at 88+ dbA at 16 volts
• Rotary switch for horn tone and three volume selections
• Outdoor products UL listed to UL 1638 (strobe) and UL 464 (horn)
outdoor requirements
• Outdoor products rainproof per UL 50 (NEMA 3R)
• Compatible with MDL sync module
Maximum Operating Pressure
250 psi
Operating Temperature Range
Indoor or outdoor use:
–40°F to 160°F (–40°C to 71°C)
Maximum Adjustment Pressure Range
4 to 20 psi
Cover Tamper Switch
UL Models: Optional P/N 546-8000
ULC Models: Factory Installed
Differential
Approximately 3 psi throughout range
Enclosure
Rated UL 4x, NEMA 4 for indoor or outdoor use
Factory Setting
Operates at rising pressure 4 to 8 psi
Shipping Weight
1.2 lbs. (.54 Kg)
Switch Contact Ratings
EPS10-1: One set SPDT (Form C)
EPS10-2: Two sets SPDT (Form C)
10.0 A, . HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Service Use
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories: NFPA 13R
National Fire Alarm Code: NFPA 72
Pressure Connection
½” NPT male glass reinforced nylon
Warranty
3 years
Dimensions
5.12˝ H × 3.325˝ W × 4.250˝ L