FL/MCP/MMF301 without an integral isolator is a
call point designed to provide a manual alarm
interface to a Firelite's fire alarm control panel.
Installation efficiency and flexibility is offered at
the heart of the call point range.
Both break glass and resettable operating
elements can be used in the standard unit.
Operation of the re-settable element is indicated
by a yellow strip on the element which becomes
visible when activated. With the addition of a
hinged transparent cover the element may be
protected against accidental operation and may
be further protected by using a cover seal which
requires breaking in order to operate the unit.
The call point uses one of 159 possible
addresses which is simply 'dialled in' using the
two rotary decade switches on the rear of the unit.
A specialist test key may be inserted into the
bottom of the unit to lower the resettable flex
portion and release the micro-switch and thus a
full functional test is achieved.
- Unique 'Plug & Play' installation concept
- Re-settable operating element option
- Analogue addressable communications
- Semi-Flush or surface Mounting
- Backward compatibility
- Enhanced aesthetics
- Extended warranty
Dimensions:
Semi-flush mounting: 89(w) x 93(h) x 27.5(d)
Surface mounting: 89(w) x 93(h) x 59.5(d)
Weight : Flush 125g
Surface 175g
Mounting hole centres: 60mm
Current Consumption:
Quiescent (without isolator)- 375μA
Alarm Current: 600μA
Operating Voltage :
15 V to 30VDC maximum
Environmental Limits:
0°C to +49°C operating temperature 10% to 93%, non-condensing relative humidity Ÿ Ingress Protection (IP) Rating : IP24D