NONE
Fully confirms IS 2189: 1988
16SWG Rugged CRCA with powder coated finish.
Modular construction.
Operates on 230V, A.C supply.
Battery backup with built in charging.
16x2 LCD Dot matrix Display.
Fire / Fault status in unambiguous coloured LED
indication.
Low battery / battery fail warning audio / visual
indication.
A.C fail audio / visual warning.
Charger fail audio / visual warning
System on, AC on, Battery on & Charger on indications
Potential Free Relay Contacts for actuators.
Lamp test facility.
One man walk test facility.
Compatible to all types of conventional detectors.
Twin RED LED indication for fire.
Zone Isolation facility with loop voltage cut off.
Earth Fault with Audio and Visual Indications.
Supervised Sounder 24v DC output for External
notification devices (Sounder, Bell, etc.).
1. Power Supply:
AC Input Supply : 230 VAC, 50Hz
DC Input Supply : 24 V DC
2. Operating Conditions : -10 to 45 C, 95 % RH Max.
3. Operating Voltage : 24 V DC
4. Normal Loop Voltage : 20.7 DC
5. Open Threshold Current : 4.2 mA
6. Short Circuit Threshold Current : 40 mA
7. Stand by Threshold Current : 8.2 mA
( EOL Current + detector's Current)
8. Alarm Current : 20 - 35 mA
9. Quiescent Current : 50mA Plus 4.2mA per Zone
10. Colour of the Panel : Semains Gray (Red, Red Texture - Optional)
11. ALARM OUTPUT:
Standard Common Output : 0.2A per Zone.
12. REMOTE INDICATION OUTPUTS
Outputs : Fire Relay Contacts (230 V 2A contact).