NONE
Rugged CRCA sheet with powder coated finish.
Operates on 220V, A.C supply
Battery backup with built in charging.
16 X 2 LCD Dot Matrix Display.
Evacuate and Key pad Enable, Disable Facility.
Low battery visual warning with audible tone.
2 Form C Relay output for fire.
One Programmable relay for fire/fault/solenoid on /timer
on.
Remote fire indication with Audible Tone.
Compatible to all types of conventional detectors.
Zone Disable (Isolation) facility with loop voltage cut off.
Resettable 24v DC output for 4 wire detectors .
Three 24V Hooter Output (Fire, after Cross zone, after gas
release) .
Two mode operation facility (Auto / Manual).
Programmable FAP input selection Facility.
Programmable Solenoid Output with On and OFF Timer.
Main / Standby Cylinder output Facility .
Gas Inhibition and Instant release facility.
Manual Gas Release with or without timer.
Actuator pressure low sensing facility.
Power
220 VAC , 50 Hz.
Wire size: 1.5 Sq. mm with 600V insulation
Battery (Lead Acid only)
Charging Voltage : 27.9 VDC.
Charging Capacity : 7 Amp Hour Battery Max.
System Quiescent Current: 80mA + (2.4mA for Detector s
Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage : Nominal 24 VDC
Alarm Current : 15 - 35mA threshold
Short Circuit Current : 40mA Maximum
Loop resistance : 50 ohms Maximum
End-Of-Line Resistor : 4.7K, 1/4watt
Standby Current : 6.8mA (2.4mA for Detectors)
Notification Appliance Circuits (Sounder/Hooter Circuit)
Operating Nominal Voltage: 24 VDC
Hooter (NACs) output : 0.5A (Each)
End-Of-Line Resistor : 4.7K, 1/4watt
Solenoid Relay Output Circuits
Operating Nominal Voltage : 24 VDC
Solenoid output : 0.75A (Each)
2No’s of Hooter (NACs) output : 0.3A (Each)
End-Of-Line Resistor: 4.7K, 1/4watt (for Solenoid Output)
Remote Outputs
Fire Contact (C, NO, NC) : 220v AC/30v DC@ 1A
Fault Contact (C, NO, NC ): 220v AC/30v DC@ 1A
Timer Contact (C, NO, NC): 220v AC/30v DC@ 1A
24 VDC Power For remote devices
Operating Voltage: 24VDC, 500mA Max.
RS 24 VDC Power For Four Wire devices
Operating Voltage: 24VDC, 500mA Max.
Dimension of the panel :
400 x 300 x 100 mm ( length x height x width)