“Ravel RE102/104 is a right blend of design, technology
and quality for Conventional range of Fire Alarm Panels.
It has been designed considering the requirements of
latest in microprocessor technology for conventional
panels ease to operate along with clear visible
indications come at an advantage for the end user.
- As per IS -2189 Standard.
- Rugged CRCA sheet with powder coated finish.
- Standby battery backup with built in charging.
- Fire / Fault status in unambiguous colored LED indication.
- Switch Mode Power Supply.
- Tactile Keypad for easy panel operation.
- System on indication.
- Main, Standby status indication.
- Low Battery visual warning with audible tone.
- Relay output for actuators for Fire and Fault.
- Lamp Test facility
- Zone wise one man walk Test Facility.
- Zone wise Isolation facility with loop voltage cut off.
- Compatible to all type of Conventional Detectors.
1) Power Supply
AC Input Supply : 220 VAC,50 Hz
DC Input Supply Voltage : 24 VDC
2) Operating Conditions : -10 to 45 C, 95% RH Max.
3) Operating Voltage : 24V DC
4) Normal Loop Voltage : 20.7 V DC
5) Open Threshold Current : 4.2 mA
6) Short Circuit Threshold Current : 40 mA
7) Stand by Threshold Current : 8.2 mA
(EOL Current + Detector Current)
8) Alarm Current : 20 - 35 mA
9) Quiescent current : 60 mA.
10) Color of the panel : Broken White,(Red, Red Texture-Optional)
11) Dimensions of panel : (350 L X 250 H X 100 D) mm
12) Approximate Weight : 4Kgs.
13) Alarm Output:
Common Hooter Output : 24V@1A
14) Remote Outputs:
Outputs : Fire, Fire Relay Contacts
(30V AC / DC @ 2A contact).