The RE – 25AR Agent Release Control Panel performs the functions of fire
suppression in a wide variety of applications. It can be used as single – hazard or
dual – hazard application with or without cross-zoning. The panel includes common
alarm, supervisory, and trouble relays, and provides unregulated auxiliary power
along with four-wire smoke power. The auxiliary relays are based on a hazard area
status. The RE – 25AR has eight inputs and four outputs, allowing for flexibility in most
single and dual hazard application for agent releasing applications.
_ 4 Class B initiating device circuit (IDC).
_ All zones accept smoke detectors and any normally open contact
device.
_ Any Zone can be configured as Alarm or supervisory Zone.
_ 2 Class B Releasing Agent Circuits (RAC).
_ 2 Class B Notification Appliance Circuits (NAC).
_ Fully complies with UL -864 9th Edition and NFPA-72.
_ Rugged CRCA sheet with powder coated finish.
_ Operates on 120 - 220v 60 / 50 Hz, AC Mains power supply.
_ Standby (battery) backup 24v DC power supply with built in charger
_ 16x2 Dot Matrix LCD Display.
_ Error free Fire / Fault status in unambiguous colored LED indication.
_ System ON indication.
_ Main, Standby status audible and visual indication.
_ Battery Low visual warning with audible tone.
_ 3 Form–C programmable relays for fault / supervisory / Fire / Cross Zone / Gas
Release.
_ Programmable 24v D.C. Outputs.
_ Programmable Mode (Auto/Manual) Selection
_ Programmable RACs.
_ Lamp Test facility.
_ Walk Test facility.
_ Zone Isolation facility with loop voltage cut off.
_ Earth fault annunciation facility at 0 ohms.
_ All field wiring circuits are Power limited except 120 / 220v AC and Battery.
_ All field wiring circuits are supervised.
_ AC Low voltage cutoff.
_ Programmable NAC’s.
_ Programmable IDC’s.
_ Programmable Supervisory Mode.
_ Programmable AC loss delay.
_ Alarm verification facility.
_ Programmable Trouble reminder facility.
Primary Power (RE-SMPS-4A-R1)
120 - 220VAC + 10% -15%, 60 / 50 Hz, 2.5Amps.
Standby Power
24v D.C (2 Nos of 12v, 12Ah Sealed Lead acid battery).
Operating Condition
Operating Temperature – 0 - 49° C / 32 - 120° F.
Relative Humidity – 93 ± 2% RH (non-condensing) at 32 ±2° C/95 ±3°F.
Charging Circuit
Charging Voltage – 28V, ±0.5V
Charging Current – 800mA (Max.).
Initiating Device Circuits - CN11
All zones are Class B Style B/C operation (Programmable).
Normal Operating Voltage: 14 - 21 VDC.
Alarm Current: 15 – 30mA.
Short Circuit Current: 45mA Maximum.
Loop resistance: 100 ohms Maximum.
End-Of-Line Resistor: 3K9, 1/2watt
Standby Current: 7mA (2mA for Detectors)
Note: For compatible devices refer Chapter 9(CD 01).
Notification Appliance Circuits – CN 7 & 8
Class – B Style - Y wiring
Operating Nominal Voltage: 24VDC – Special Application
Current for all NACs: 1.2Amps (0.6A per circuit)
Current Limit: via Thermal Fuse
Line Drop: 1.8V
End-Of-Line Resistor: 3K9, 1/2watt