The ZX2Se is an intelligent analogue addressable fire alarm
control panel. It has been designed and constructed around
proven and reliable microprocessor technology. This simple
approach has produced a modular, scalable fire alarm
platform suitable for protecting all types of premises.
The ZX2Se control panel supports a total of five industry
leading protocols, allowing fire detection devices to be
independently selected based on performance or aesthetic
appeal. The ZX series control panels seamlessly integrate
with Apollo (Xplorer, XP95 & Discovery), Hochiki ESP, Nittan,
Morley-IAS and System Sensor detection device protocols.
Designed for maximum flexibility, the ZX2Se control panel is
supported by a complete suite of peripherals and software
tools. Information on the location of fires, faults and system
status can be easily displayed or printed in multipl
locations. Integration with Voice Evacuation Systems, paging
systems and third party control systems is supported through
a range of peripheral interface units.
• Multi-protocol
• Modular concept
• Simple, robust design to EN54
• Intuitive to use
• Easy to maintain
• Easy to expand
• Easy to network
• Easy to install
• Easy to configure
Operating Voltage 230V 50Hz AC
(+10%, -15% voltage tolerance)
Max. PSU Rating
2.5A total, comprising: Battery Charger: 0.5 Amp
Internal & External Loads
General System Load: 1.8A @ 24V nominal
Max Loop Load: 460mA
Standby Batteries 24V sealed lead acid batteries
Minimum Capacity: 2x 12V 7Ah
Maximum Capacity: 2x 12V 12Ah
Dimensions (mm) 400 x 400 x 135 (H x W x D)
Weight 10 kg without batteries
Environmental Operating Limits
Temperature: 0°C to +40°C
Humidity: 85% non-condensing (maximum)
Construction Sheet steel painted, sealed to IP30
Cable Entry 14 x 20mm knock-outs in top of cabinet
2 x 20mm knock-outs in bottom of cabinet
Loop Capacity 1 or 2 Loops 460mA per loop maximum
Apollo, Nittan and Hochiki Protocols:
Max. 126 devices (detectors and modules) per loop
Morley-IAS and System Sensor Protocols:
Max. 99 sensor and 99 module addresses per loop
Note: Mulitiple sensor protocols cannot be used in the panel simultaneously.
Zones Up to 20 zone with individual LED indicators.
Internal Sounder Intermittent buzzer (fault condition) Highpitched continuous buzzer (fire condition)
External Outputs
Sounder Outputs 2 programmable outputs. Open and short circuit monitoring. 1A maximum per output.
Auxiliary Relays 1 fault and 1 fire relay voltage free, changeover outputs Contacts rated at 24V AC/DC, 1A, 0.6 PF maximum.
User Controls
SOUND ALARMS, SILENCE/ RESOUND, MUTE BUZZER, ACCEPT, SYSTEM RESET
Programming Controls
Alphanumeric multi-level keypad with 15 keys and 5 control keys: YES, NO, CHANGE, ENTER and SHIFT
LED type general panel status indicators
FIRE, FAULT, ACKNOWLEDGED, DISABLEMENT, TEST, SOUNDER FAULT, DELAYED MODE, RELAYS DISABLED,EARTH FAULT, SYSTEM /CPU FAULT, SOUNDERS DISABLED, ALARMS SILENCED, SUPPLY FAULT, POWER.
LED type zone Indicators (for 20 zones)
FIRE, FAULT/TEST/DISABLED
Display
4x40-character LCD alphanumeric display with back-light.
Serial Interface
2 serial ports with connections for optional RS485 or RS232 plug-in communication cards.
Networking
Maximum 99 panels can be networked using a Master Network and connected Sub-Networks.