The Dimension series of intelligent multi protocol fire alarm
control panels from Morley-IAS Fire Systems have been
developed based on two concepts - simplicity and reliability
Simply, fix the control panel to the wall, connect the
field wiring and everything else is configured in the
software. Even programming the control panel is
simple. No computer is required and it only takes a
few key presses to have a working fire alarm system.
First, set the protocol for the loop devices. Second,
“Autolearn” the panel and finally, “Reset” the panel.
The control panel is now protecting the building.
The Dimension series provides additional features
allowing:- programmable text messages to identify the
exact location of each field device, a class change
input for schools, coincidence and verification
detection (false alarm management), sensitivity
adjustment (between day and night), programmable
function buttons, input/output logic and extensive
event logging. A feature rich fire alarm control panel
constructed from high specification components to
help both the installer and the end user.
• Complies with EN54 part 2 and part 4
• 40 fire zone LED indicators
• 2 independent sounder circuits
• 500mA Universal Loop Driver
• Supports Apollo (Xplorer, XP95 and
Discovery), Hochiki (ESP), Morley-IAS &
System Sensor
• 7 day timers
• Day/Night mode switching
• Onboard monitored inputs
• Programmable user function keys
• Event logging
• Onboard diagnostics
• User access restriction
• All metal enclosure
• Plug-in connectors
• Optional internal printer
• PC configuration software (optional)
Mechanical
Dimensions (H x W x D):
DX1e-20S 245 x 380 x 110 mm
DX1e-40M 380 x 380 x 130 mm
DX1e-40MP 380 x 380 x 130 mm
Weight (Excluding batteries):
DX1e-20S(F) 5 Kg DX1e-40M(F) 7 Kg DX1e-40MP(F) 7.2 Kg
Material 1.2mm Zintec powder epoxy coated
Colour RAL 9001 - Cool Grey
Knockouts Top: 19 x M20 Bottom: 3 x M20.
Temperature Operating: 0°C to +45°C Storage: 10°C to +55°C
Relative Humidity 5% to 95% non condensing.
Electrical
Operating voltage 230Vac (+10%, -15%) 50-60 Hz
PSU Rating DX2e-40M(F) 24 Vdc 4A DX2e-40MP(F) 24 Vdc 4A
DX2e-40L(F) 24 Vdc 4A DX2e-40LP(F) 24 Vdc 4A
Standby Batteries
DX2e-40M(F) 2 x 7Ahr or 2 x 12AHr
DX2e-40MP(F) 2 x 7Ahr or 2 x 12AHr
DX2e-40L(F) 2 x 12AHr or 2 x 17AHr
DX2e-40LP(F) 2 x 12AHr or 2 x 17AHr
Auxiliary output* +24 Vdc 250mA fused
Loop Capacity** 2 Loops, 500mA, 126 devices Apollo Protocols,
126 devices Hochiki Protocol, 198 devices Morley-IAS Protocol,
198 devices System Sensor Protocol
Output Relays
Fire relay: Single pole changeover 30Vdc 1A
Fault relay: Single pole changeover 30Vdc 1A
Aux relay: Programmable single pole changeover 30Vdc 1A
Onboard Inputs Keyswitch: programmable for select functions
Input #1: programmable (monitored) for select functions
Input #2: programmable (monitored) for select functions
Data Ports
1 x RS 485 (Repeater connections) 1 x RS232 (PC Programming)
Sounder Circuits 2 output circuits, 1A available across both circuits.*