The Dimension series of intelligent multi protocol fire alarm control panels from Morley-IAS Fire Systems have been developed based on two concepts - simplicity and reliability.
Simply, fix the control panel to the wall, connect the field wiring and everything else is configured in the software. Even programming the control panel is simple. No computer is required and it only takes a few key presses to have a working fire alarm system. First, set the protocol for the loop devices. Second, “Autolearn” the panel and finally, “Reset” the panel. The control panel is now protecting the building. The Dimension series provides additional features allowing:- programmable text messages to identify the exact location of each field device, a class change input for schools, coincidence and verification detection (false alarm management), sensitivity adjustment (between day and night), programmable function buttons, input/output logic and extensive event logging. A feature rich fire alarm control panel constructed from high specification components to help both the installer and the end user
• Complies with EN54 part 2 and part 4
• Optional 20 or 40 fire zones
• 2 independent sounder circuits
• 500mA Universal Loop Driver
• Supports Apollo (Xplorer, XP95 and
Discovery), Hochiki (ESP), Morley-IAS &
System Sensor
• 7 day timers
• Day/Night mode switching
• Onboard monitored inputs
• Programmable user function keys
• Event logging
• Onboard diagnostics
• User access restriction
• All metal enclosure
• Plug-in connectors
• Optional internal printer
• PC configuration software (optional)
Mechanical
Dimensions (H x W x D):
DX1e-20S 245 x 380 x 110 mm
DX1e-40M 380 x 380 x 130 mm
DX1e-40MP 380 x 380 x 130 mm
Weight (Excluding batteries):
DX1e-20S(F) 5 Kg DX1e-40M(F) 7 Kg DX1e-40MP(F) 7.2 Kg
Material 1.2mm Zintec powder epoxy coated
Colour RAL 9001 - Cool Grey
Knockouts Top: 19 x M20 Bottom: 3 x M20.
Temperature Operating: 0°C to +45°C Storage: 10°C to +55°C
Relative Humidity 5% to 95% non condensing.
Electrical
Operating voltage 230Vac (+10%, -15%) 50-60 Hz
PSU Rating DX1e-20S(F) 24 Vdc 3A
DX1e-40M(F) 24 Vdc 3A DX1e-40MP(F) 24 Vdc 3A
Standby Batteries
DX1e-20S(F) 2 x 7AHr DX1e-40M(F) 2 x 7Ahr or 2 x 12AHr
DX1e-40MP(F) 2 x 7Ahr or 2 x 12AHr
Auxiliary output* +24 Vdc 250mA fused
Loop Capacity** 1 Loop, 500mA, 126 devices Apollo Protocols, 126 devices Hochiki Protocol, 198 devices Morley-IAS Protocol, 198 devices System Sensor Protocol
Output Relays
Fire relay: Single pole changeover 30Vdc 1A
Fault relay: Single pole changeover 30Vdc 1A
Aux relay: Programmable single pole changeover 30Vdc 1A
Onboard Inputs Keyswitch: programmable for select functions
Input #1: programmable (monitored) for select functions
Input #2: programmable (monitored) for select functions
Data Ports
1 x RS 485 (Repeater connections) 1 x RS232 (PC Programming)
Sounder Circuits 2 output circuits, 1A available across both circuits.*