The Morley-IAS micro monitor module is used in
conjunction with the ZX series intelligent multi protocol
fire alarm control panels, provides an interface between
the normally-open contact alarm initiating devices.
Though the module can be used to monitor an entire
zone circuit, it is ideally suited for monitoring single
devices. The module is small enough to fit inside a
single-gang junction box behind the device being
monitored. The small size and lightweight allow it to
be installed without the need to be rigidly mounted.
Used to monitor a single device or a zone of 4-wire
smoke detectors, manual call points or pull stations,
waterflow devices, or other normally open dry-contact
devices. A 47K Ohm end-of-line resistor (provided)
terminates the circuit. Controls include two rotary
switches for direct dial entry of DECADE address (01-99).
Each module uses one of 99 available module addresses
on loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/
short) of its zone.
• Built-in type identification automatically identifies this device as a monitor module to the control panel
• No additional power required
• High noise (EMF/RFI) immunity
• Tinned, stripped leads ease of wiring
• Direct dial entry of DECADE address (01-99)
mechanical
Dimensions (HxWxD) : 40 x 48 x 13 mm
Weight: 33 gr. (1 oz)
Operating temperature: -10°C to 60°C
Relative humidity: 10% to 93%
non-condensing
electrical
Operating voltage: 15 to 32 Vdc
Stand-by current: 375 μA (24 Vdc) maximum
Alarm current: 5.1 mA (24 Vdc) LED on
Supervisory loop:
Normal 100 μA
Short 150 μA