The MI-MCP-GB is designed to provide a manual alarm
interface to the Morley-IAS ZX series intelligent multiprotocol
fire alarm control panels.
The units are fitted with a built-in monitoring module,
which provides an interface to the detection loop. The
address of the call point is simply “dialed in” using the
rotary switches on the rear of the unit.
The call points may be used in most environments as a
convenient and quick way of raising an alarm. It is
generally installed by exit doors to be operated as
people leave a building.
For surface mounting a M500KACGB, a matching plastic
back box complete with cable terminations is used. If
flush mounting is required a single gang, standard
electrical knock-out box may be used in conjunction
with a terminal tray for cable connection.
• Direct decade addressing (01-99)
• Built-in electronics
• Fast response
• LED shows polling (optional) and activation
• Flush or surface mounting
• Up to 99 per loop (+99 analogue sensors)
• LPCB approved
• Simple to test
• Designed to the requirements of BS5839, Part 2
• IP67 rated model
mechanical
Operating temperature: - 10°C to 60°C
Humidity: 10% to 93%
non-condensing
MI-MCP-GB:
Dimensions (HxWxD):
Surface: 87 x 87 x 52 mm
Flush: 87 x 87 x 33 mm
Weight: 125 gr.
MI-MCPW-GB:
Dimensions (HxWxD): 124 x 124 x 60 mm
Weight: 375 gr.
electrical
Operating voltage: 15 to 32 Vdc
Current consumption:
Stand by current: 200 μA @ 24 Vdc
LED current: 7 mA @ 24 Vdc