Simple, yet clever in concept the sounders and beacons
employ technology to maximise sound and light output,
focus sound distribution, simplify installation and
maintain high efficiency and reliability.
Easy to install
One simple two stage installation process. Firstly, fix the
base connection plate, terminate the loop wiring and
test the wiring. Secondly, select the output device
required (sounder, beacon or combined sounder beacon)
and fit the unit to the base.
Easy to adjust
Simply twist the unit off it’s mounting and re-configure
the settings to pick any of 32 sounder tones at any of 3
volumes.
· Easy to install
· Easy to adjust
· Simple to maintain
· 32 built in tones
· CPD Approved
· LPCB Approved to EN 54 part 3
· Low power requirements
· High power LED beacon
· Optional IP65 rating
· Optional built-in isolator)
electrical
Operating voltage: +15Vdc to +28Vdc
Operating current (24Vdc):
No communication
Quiescent (no isolator): 300μA
Quiescent (isolator): 490μA
With communication once every 5 seconds
Quiescent (no isolator): 450μA
Quiescent (isolator): 640μA
Alarm Current: Refer to table 1.
Beacon Alarm Current: 1.7mA (without isolator)
Environmental
Relative Humidity: 10-96% non-condensing
Operating Temp: -25°C to +70°C
Ingress protection :
Wall units: IP33C
Wall units Plus WDBR: IP65
Base units: IP21C
Colour
RED: RAL 3000
Detector White: RAL 9001
Wall Sounder White: RAL 9010