The 40-Way programmable mimic driver is a compact
remote I/O device for the ZX series intelligent multi
protocol fire alarm control panels. This device, along
with other remote I/O devices, the repeater units and
the external printer provide a complete range of
peripheral devices to further enhance the functionality
and expandability of the ZX series systems.
The 40-way mimic driver card consists of 40 open
collector outputs built on a single printed circuit board.
The outputs can provide up to 15mA each to drive
mimic LEDs (or other low-current external loads) and
can be programmed to follow a zone or an event in the
master panel.
The AUTO-LEARN facility in the ZX series control panels
automatically determines the number of modules
connected to the peripheral bus and add each mimic
driver card to the list of outputs in the panel. Once the
mimic driver cards are learned, then each of these cards
can be programmed to follow a group of 40 zones or
events on the system (e.g. zones 1-40, 41-80, etc., events
1-40, 41-80, 81-120, etc.).
• Provides 40 programmable open-collector outputs
• Compatible withZX series intelligent multi protocol fire alarm contol panels
• RS485 communication
• Connects to the peripheral bus (port D) on the fire alarm panel
• Up to 31 on a peripheral bus
• Zone or event operation
• Easy DIP switch addressing
• 12 to 24V switching capability
mechanical
Dimensions (HxWxD): 113 x 160 x 29 mm
Weight: 226 gr. (8 oz)
Operating temperature: 0°C to 49°C
Humidity: 10% to 93%
non-condensing
electrical
Operating voltage: 18 to 28 Vdc
Current consumption:
Stand by: (all outputs off) 19mA @ 18 Vdc
29mA @ 24 Vdc
39mA @ 28 Vdc
Full load: (all outputs on) 370mA @ 18 Vdc
277mA @ 24 Vdc
247mA @ 28 Vdc
Note - An additional 15mA per output must be added when the on-board power supply is used to drive the external load(s). A suitable current limiting resistor required in series with the LED(s) to limit the output current to 15mA. Power consumption:
On-board power source:
Vss (nom): 6.5 to 7.0 Vdc
Iss (max): 15mA per output
External power source:
Vss (ext): min. 12Vdc,max. 24 Vdc
Iss (max): 15mA per output
LED indicators:
485RX: Yellow, flashes when mimic card receives vaild data. PWR: Green, flashes at a rate of 1Hz when mimic card has a DC supply and is operating. Screw terminals: Maximum cable cross sectional area 2.5 mm2. (13 AWG) removable block.
Wiring: